Firestop
A firestop or fire-stopping is a form of passive fire protection that is used to seal around openings and between joints in a fire-resistance-rated wall or floor assembly. Firestops are designed to maintain the fire-resistance rating of a wall or floor assembly intended to impede the spread of fire and smoke.
Description
Firestops prevent unprotected horizontal and vertical penetrations in a fire-resistance-rated wall or floor assembly from creating a route by which fire and smoke can spread that would otherwise have been fire resisting construction, e.g. where a pipe passes through a firewall.Fire stopping is also to seal around gaps between fire resisting constructions, e.g. the linear gap between a wall and the floor above, in order for construction to form a complete barrier to fire and smoke spread.
Opening types
Firestops are used in:- Electrical, mechanical, and structural penetrations
- Unpenetrated openings
- Re-entries of existing firestops
- Control or sway joints in fire-resistance-rated wall or floor assemblies
- Junctions between fire-resistance-rated wall or floor assemblies
- Head-of-wall joints, where non-load-bearing wall assemblies meet floor assemblies
Classification for penetrations and the barriers they penetrate, are categorized by a standardized letter-number system that has been adopted by all firestop products manufacturers. A typical system would consist of several letters, followed by a series of numbers indicating the type of penetrant that is passing through the particular barrier ex:
Materials
Components include intumescents, cementitious mortars, silicone, firestop pillows, mineral fibers, and rubber compounds.Maintenance
Firestops should be maintained in accordance with the certification listing. Construction documentation sometimes includes an inventory of all firestops in a building, with drawings indicating their location and certification listings. Using this, a building owner can meet the fire code relating to fire barriers. Improper repairs may otherwise result, which would violate the fire code and could allow a fire to travel between areas intended by code to be separated during a fire.Ratings
Firestop materials are not rated per se. They receive a fire rating by combining materials in an arrangement specific to the item penetrating the fire-rated wall or floor and the construction arrangement of the fire-rated wall or floor. A two-hour-rated pipe-penetration firestop may consist of a layer of caulking over packed mineral wool. The arrangement, not the caulking, provides the two-hour rating. The individual firestop materials and the overall firestop assembly are listed.Testing and certification
Certification listings include those available from:- Underwriters Laboratories
- Underwriters Laboratories of Canada
- Deutsches Intitut für Bautechnik
- Efectis
- FM Global
Regulations and compliance