Hammersmith power station
Hammersmith power station supplied electricity to the London Borough of Hammersmith from 1897 to 1965. It was owned and operated by the Hammersmith Vestry and then the Hammersmith Metropolitan Borough Council until the nationalisation of the British electricity supply industry in 1948. The power station was frequently redeveloped with new plant over its operational life to meet increased demands for electricity. It was decommissioned in 1965.
History
In 1893 the Hammersmith Vestry applied for a provisional order under the Electric Lighting Acts to generate and supply electricity to the parish. The was granted by the Board of Trade and was confirmed by Parliament through the Electric Lighting Orders Confirmation Act 1893. The power station was built off Fulham Palace Road, north of Yeldham Road and first supplied electricity on 21 June 1897 to a potential population of 104,000.Equipment specification
The original 1898 plant at Hammersmith power station comprised Bellis and McClaren engines directly coupled to Ferranti flywheel disc alternators. In 1899 2xE.C.C.-Robey 300-kW steam alternators had been added totalling 3x175kW and 3x300kW machinesThe power station was then enlarged to allow an three additional boilers to power two Robey engines with Siemens iron core alternators of 600 kilowatts output.
| Year | Generating capacity, kW | Maximum connected load, kW |
| 1898 | 400 | 317 |
| 1899 | 1,275 | 550 |
| 1904 | 2,500 | 1,596 |
| 1913 | 10,300 | 5,788 |
| 1919 | 10,300 | 8,389 |
Inter-war plant
Following the First World War further new plant was installed to meet growing demand for electricity.In 1920 a 10,000 kW Parsons turbo alternator set running at 3000 rpm was installed and by 1923 the generating plant comprised:
- Coal-fired boilers generating up to 190,000 lb/h of steam, these supplied steam to:
- Generators
- * 1 × 1,500 kW steam turbo-alternator
- * 2 × 2,000 kW steam turbo-alternators
- * 1 × 3,000 kW steam turbo-alternator
- * 1 × 10,000 kW steam turbo-alternator
The plant installed in 1919 included the UK's first large pulverised fuel fired boilers, these were provided on three of the units used a bin feed system. Hydraulic coal delivery was also introduced at Hammersmith.
A choice of electricity supplies were available to consumers:
- 2-phase, 50 Hz AC at 110 and 220 Volts
- 3-phase, 50 Hz AC at 110 and 220 Volts.
New plant 1937
By 1954 the plant comprised:
- Boilers:
- * 1 × 17,000 lb/h Stirling boilers with chain grate stoker,
- * 2 × 20,000 lb/h Stirling boilers with chain grate stokers,
- * 1 × 37,000 lb/h Stirling boilers with chain grate stoker,
- * 3 × 45,000 lb/h Stirling boilers with chain grate stokers,
- Turbo-alternators:
- * 2 × Parsons 10 MW turbo-alternators, 3000 rpm, generating at 6.6 kV
Operations
Operational data for the early years of operation was as follows:| Year | Number of consumers | Public Lamps connected | Electricity sold, MWh |
| 1898 | 132 | 87 | 234.8 |
| 1899 | 275 | 372.2 | |
| 1904 | 1,469 | 252 | 2,223.9 |
| 1912 | 3,329 | 866 | 9,167.9 |
| 1919 | 4,603 | 880 | 15,962.8 |
| 1920 | 5,068 | 942 | 13,779.9 |
There was a growth in the number of consumers and the amount of current sold within yearly variations.
Operating data 1921–23
The operating data for the period 1921–23 is shown in the table:Under the terms of the Electricity Act 1926 the Central Electricity Board was established in 1926. The CEB identified high efficiency ‘selected’ power stations that would supply electricity most effectively. The CEB also constructed the National Grid to connect power stations within a region. Hammersmith power station was electrically connected to Fulham power station via twin 66 kV underground cables and to Barnes power station via triple 6.6 kV underground lines.
Operating data 1937 and 1946
Hammersmith power station operating data, 1937 and 1946 is as follows.| Year | Load factor per cent | Max output load, MW | Electricity supplied GWh | Thermal efficiency, per cent | Customers |
| 1937 | 39.1 | 23,850 | 74.803 | – | 35,079 |
| 1946 | 13.6 | 16,032 | 19.095 | 12.6 | – |
The British electricity supply industry was nationalised in 1948 under the provisions of the Electricity Act 1947. The Hammersmith electricity undertaking was abolished, ownership of Hammersmith power station was vested in the British Electricity Authority, and subsequently the Central Electricity Authority and the Central Electricity Generating Board. At the same time the electricity distribution and sales responsibilities of the Hammersmith electricity undertaking were transferred to the London Electricity Board.
Operating data 1954–65
Operating data for the period 1954–65 is shown in the table:| Year | Running hours or load factor | Max output capacity MW | Electricity supplied GWh | Thermal efficiency per cent |
| 1954 | 593 | 17 | 3.436 | 7.73 |
| 1955 | 718 | 17 | 3.937 | 7.63 |
| 1956 | 502 | 17 | 3.518 | 7.60 |
| 1957 | 178 | 17 | 0.741 | 3.49 |
| 1958 | 267 | 17 | 1.136 | 4.77 |
| 1961 | 1.1 % | 15 | 1.492 | 5.68 |
| 1962 | 1.6 % | 15 | 2.147 | 6.63 |
| 1963 | 3.77 % | 15 | 4.953 | 9.30 |
| 1964 | 2.85 % | 15 | 3.461 | 8.82 |
| 1965 | 4.2 % | 15 | 5.462 | 8.72 |
The data demonstrates the less intensive use of the power station during its last decade of operating life.
The electricity supplied, in MWh, by Hammersmith power station over its operating life was: